Understanding the Accuracy Class of Current Transformers (Protection Class)
Current transformers and voltage
transformers are extensively used in power system to scale down the operating
current and voltage. The scaling down of the current and voltage is required
chiefly for measuring, metering and protection purposes. The relays and other
measuring instrument operates and tolerates much lower values of current and
voltage for their safe operation.
In terms of usage,
CTs are broadly classified as Protection CT or Metering CT. This article shall
focus on Protection Class Current Transformers. It is imperative here to
mention the instrument transformers (CTs & VTs) may have multiple cores, in
which case separate cores may be used for metering and protection purposes, all
in one instrument transformer. Multi Core CTs and VTs may have different
designated class for each core.
Before dwelling into explaining accuracy class of Current Transformers let us first outline the following terms:
Before dwelling into explaining accuracy class of Current Transformers let us first outline the following terms:
Accuracy Limit Factor
At the time of fault, heavy
current flows through the Current Transformers therefore it is important that
the CT must maintain appropriate amount of accuracy during high saturation
conditions. Accuracy limit factor signifies the current limit up till which the
performance of the CT shall remain sufficiently accurate. It is expressed in
terms of multiple of the rated current.
Burden
The burden of the Current
transformer is the impedance presented to the secondary of the CTs. The burden
is essentially due to the CT internal impedance, connecting wire impedance and
any device such as relay or meter connected to the secondary. The burden is
usually expressed in Volt Amperes (VA) or ohms.
Composite Error (Ratio Error
& Phase displacement)
Due to the saturation of the
core, the secondary current is not the exact multiple of the primary current,
this is known as ratio error. In addition the phase displacement between the
primary and reversed secondary current must be ideally zero however there is
some displacement which is known as phase displacement error. Composite error
is defined by IEC 61869 as the R.M.S value of the difference between
primary and secondary current. The composite error includes ratio error, phase displacement
and error due to harmonics.
Accuracy Class of Current Transformer
IEC 61869-2 defines the accuracy
of the current transformer for protection purposes. The preferred accuracy
classes are 5P (5 percent maximum error) and 10P (10 percent maximum error). IEC
associates accuracy limit factor as well. The most commonly used values for ALF
are 10 and 20. For Example We have a current transformer whose name plate reads
as 30 VA 5P20, which means 30 VA the maximum burden that can be fed with CT and
5% error at 20 times of the rated current.
Class PX Current Transformer
PX class transformer are normally
used for unit protection scheme such as for bus bar protection. Where transient
performance are critical to safe operation of the protection scheme. Knee Point
Voltage, Exciting Current at knee-point and Secondary Impedance are important
characteristics that define PX class CT.
Knee Point voltage is a point in excitation curve at which 10%
increment of voltage would require an increase of 50% in excitation current.
IEEE defines two fundamental
relaying accuracy designations, one headed by a “C” and the other by a “T”
designation. T class accuracy CTs are seldom used today. C class designation is
usually followed by a number which represents the secondary terminal voltage
the CT (C200, C400 etc.) will maintain operating with in error limits. The C
designation limits the ratio error to 10% at 20 times the rated current. So
secondary terminal voltage has direct relation to the burden of the CT. However,
in IEEE, the secondary burden has a 60-degree impedance angle, whereas in IEC
the secondary burden is purely resistive. Therefore, an IEEE current
transformer with a limiting error of 10 percent with the IEEE burden will have
a limiting error of 5 percent with the IEC resistive burden. Therefore, for IEC
equivalency, the accuracy is a 5P class rather than 10P. A table is presented
below as an example showing IEEE and IEC equivalent.
200
|
B-2.0
|
2.0
|
C200
|
50VA-5P20
|
400
|
B-4.0
|
4.0
|
C400
|
100VA-5P20
|
Expressing Burden in Ohms (An-Example)
Considering the example of CT rated as 100/5 Amps 30 VA
5P20
Volt Amperes = 30 VA
Secondary Rated Current = 5 A
Therefore
Secondary Rated Voltage = 30/5 = 6 V
Burden in Ohms = 6/5 = 1.2 Ohms
About the Author


Comments
Post a Comment