Understanding the Rated Characteristics of Medium Voltage and High Voltage Circuit Breakers
Circuit Breakers are
extensively used in power systems to make or break electrical circuit during
normal operation as well as during fault conditions. Circuit Breaker must be
able to withstand the thermal and electrodynamic stresses arise due to
interruption of operating currents and short circuit currents during fault
conditions. There are various types of circuit breakers (Air Blast CB, OCB, SF6
Breakers, VCBs), however the typical ratings that characterize the operation of
circuit breaker in a power system remains the same.
Rated Voltage
It is the maximum RMS Voltage at
which the breaker is designed to operate safely and satisfactorily. Rated
Voltage is always greater than the operating voltage. For Example a breaker
operating in a 132 kV Network may be rated at 145 kV or a medium voltage
breaker in 11kV Network at 15kV or 17.5kV. Common Values of rated voltages are
15kV, 17.5 kV, 24kV, 36kV, 145kV, 245kV and so on.
Rated Frequency
50 Hz and 60 Hz frequency systems
are the most commonly used systems around the world. The breaker is designed to
operate on the system frequency.
Rated Normal Current
It is the RMS Value of the
current, Circuit Breaker is designed to carry continuously in closed position,
operating within permissible temperature rise limits as defined by IEC 62271-1
at an ambient temperature of 40oC.
Rated Insulation Level
The ability a breaker to
withstand switching and lightning surges is defined by the following:
Lightning Impulse Withstand Voltage
It defines the
ability of the breaker to withstand the overvoltage arising due to lightning
strikes. Since lightning is a natural phenomenon and its shape and size cannot
be predicted, therefore basic impulse loading is defined for the impulse wave
shape of 1.2/50 µsec. The most commonly used values for BIL is presented in
the table.
1.2/50 µsec is the most commonly used wave shape
however different standards have been in practice as well.
Power
frequency withstand Voltage
It is the
ability of the system to withstand the voltage at system frequency for 1 min.
Rated
Voltage
|
Impulse
Withstand Voltage
|
Power
Frequency Withstand Voltage
|
KV
|
kV
|
kV
|
17.5
|
95
|
38
|
145
|
650/750
|
275/315
|
245
|
900/1050
|
460/530
|
Table 1 Insulation
Levels for Different Systems
Rated Short Time
Withstand Current
It is the RMS value of the
current circuit breaker is expected to carry for a specified short time. The
short time is usually 1 sec. or 3 sec. The value of rated short time current is
normally equal to short circuit current.
Rated Short Circuit
Current
Also called rated short circuit
breaking current, it is the max. value of short circuit current that the
circuit breaker is expected to break at its rated voltage.
Rated Peak Withstand
Current or Rated Making Current
The circuit breaker is expected
to withstand the peak associated with the first major loop of short circuit
current. This is particularly important in case of circuit breaker (accidental)
closing when the fault is already present. The rated making current for the
circuit breaker is equal to 2.5 times of the short circuit current for 50Hz
system, and 2.6 times for 60Hz system.
Operating Sequence
It designates the switching
sequence of the circuit breaker. The operating sequence as per IEC is O - t -CO
- t’ – CO. where t and t’ are 0.3 sec or 3 min depending upon the requirement
of switching operations. O represents opening operation and CO represent opening
operation immediately after closing.
Rated Transient
Recovery Voltage
It is the voltage that appears
across the terminal of the circuit breaker after the interruption of current.
This voltage appearing across the terminal may be many times greater than the
nominal voltage depending upon the configuration & system earthing, the
breaker must be able to break all short circuit currents at all transient
recovery voltages below rated TRV.
First Pole to Clear
Factor
It is the ratio of recovery
voltage across the 1st pole of the circuit breaker to normal phase to ground voltage
across the terminal of the circuit breaker. The circuit breaker breaks the
current at zero instant, since zero is reached at different instant for each
phase, the high recovery voltage appears across the pole, opened first. The Value
of FPC factor depends upon the system grounding and is usually taken as 1.5 or
1.3 depending upon the neutral earthing.
Rated Out of Phase
Breaking Current
It is the maximum value of
current, circuit breaker is expected to break when the system phases are not
synchronized. The voltage appearing across terminal of the circuit breaker increases
many times in such a scenario. This is an important parameter for generator
circuit breakers. It’s value is usually 25% of the short circuit breaking
current.
Rated Cable Charging
Breaking Current
It is the RMS value of the
current circuit breaker is designed to break during switching of unloaded
cables.
Rated Line Charging
Breaking Current
It is the RMS value of the
current circuit breaker is designed to break during switching of unloaded transmission
lines.
Switching of Small
Inductive Current
Not only the fault interruption current
capability is important, When the circuit breaker breaks or switches a smaller
inductive current, significant overvoltage may occur which may damage the
insulation of inductive load such as unloaded transformer.
Electrical Endurance
IEC 62271-100 defines two electrical Endurance Classes for circuit
breaker, Class E1 designates basic electrical endurance and Class E2 designates
extended electrical endurance, Class E2 circuit breaker do not require maintenance
of the interrupting part during their expected life.
Mechanical Endurance
As per IEC 62271-100, two mechanical endurance classes,
Class M1 (2000 Operations) and Class M2 (10,000 Operations) are defined.
About the Author
About the Author

Comments
Post a Comment